Specifications
for Variable
Speed Packaged Pumping System Open System
Furnish and install one EnviroSep Model PPS-VO- [A] - [B] - [C] -
[D] Packaged Pumping System with the system capacity to pump _________
GPM of _____________ (fluid) from __________psig to __________psig.
KEY:
[A] =
Model # (GPM)
[B] =
# of pumps (1,2,3,etc.)
[C] =
Parallel (P) or Stand-by (S) pump designation
[D] =
Manual (M) or Automatic (A) alternation for multiple pumps
GENERAL
- This package shall be factory assembled with pump(s), fabricated
steel frame, interconnection piping( welded per ASME Section IX certified
welders), UL-listed Industrial Control Panel factory wired for single-point
field connection per NEC.
PUMPS
- Pump(s) shall be single, end-suction type with radically split,
top center-line discharge, self-venting casing. Pump construction
shall be cast iron, bronze fitted and shall be fitted with a long-life,
product lubricated, drip tight mechanical seal, with O-ring seat retainer.
Impeller shaft to be 416SS fitted with a SS shaft sleeve and be supported
by two heavy duty ball bearings. The design shall allow back pull
out servicing, enabling the complete rotating assembly to be removed
without disturbing casing piping connections. The pump shall be mounted
on a rigid, single base plate and by flexible with guard to the motor.
Seal shall be rated for continuous duty at 270oF, motor shall be open
drip proof, NEMA MG-1 with 1.15 service factor
TRIPLE
DUTY VALVE - System shall include, on the discharge of each pump,
a combination valve incorporating three functions in one body: tight
shut-off, spring closure type silent non-slam check, and flow measured/throttling.
Valve body shall be ductile icon with two ¼" NPT connections
on each side of the valve seat. The valve disc shall be bronze plug
disc type with high impact engineered resin seat to ensure tight shut-off
and silent check valve operation. Valve stem shall be SS with flat
surfaces provided for adjustment with open end wrench.
AIR REMOVAL
EQUIPMENT - System shall include one tangential air separator with
internal stainless steel collector tube. Connections to be flanged
with a rating of 150 psig. System shall be equipped with ¾"
Pressure Relief Valve, ¾" Pressure Regulating Valve, ASME
Compression / Expansion Tank (sized by or provide system volume and
temperature difference), and tank fitting, sight glass, and tank drain
connections to tank. Bladder-type expansion tank may be substituted
as alternate.
VARIABLE
FREQUENCY DRIVE - Variable Frequency Drive shall be variable torque
AC inverter enclosed in NEMA 1 or 12 enclosure. Standard features
shall include circuit breaker disconnect, Hand-Off-Auto selector switch,
manual potentiometer (speed pot), door-mounted keypad, run relay contacts,
fault relay contacts, and top/bottom conduit entry. Drive bypass shall
be provided as standard with Drive-Off-Bypass selector switch. Class
20 overloads are included.
SUCTION
DIFFUSER - System shall include, on the suction of each pump a suction
diffuser with cast iron body, outlet guide vanes and removable SS
strainer.
CONTROL
PANEL - System shall include one (1) UL - Listed, NEMA 12, Industrial
Control Panel with single-point power connection, pre-wired to all
electrical components. Panel shall have thru-the-door fused disconnect;
magnetic circuit breaker supplementary motor protector with fast-closing
contacts, non-reversing 3-pole contactor, and variable setting, bi-metallic
overload relay for each motor; 30 mm Foundry-duty switches; 30 mm
Corrosion Resistant pilot lights; control transformer; Automatic Alternator
(if required). Operation of each pump shall be Hand-Off-Auto with
external connection to terminal blocks. When standby pump(s) are used,
the standby pump(s) shall manually/automatically(customer specified)
start on primary pump failure. All internal wiring shall be placed
in conduit.
MANUFACTURER
- Shall assume system liability, and performance guarantee and warranty
all equipment on system for 12 months after initial start-up.
Return
to Variable Speed System with Variable