KEY:
[A] = Model # (GPM)
[B] = # of pumps (1,2,3,etc.)
[C] = Parallel (P) or Stand-by (S) pump designation
[D] = Manual (M) or Automatic (A) alternation for multiple
pumps
GENERAL - This package shall be factory assembled with
pump(s), fabricated steel frame, interconnection piping( welded per
ASME Section IX certified welders), UL-listed Industrial Control Panel
factory wired for single-point field connection per NEC.
PUMPS - Pump(s) shall be single, end-suction type with
radically split, top center-line discharge, self-venting casing. Pump
construction shall be cast iron, bronze fitted and shall be fitted with
a long-life, product lubricated, drip tight mechanical seal, with O-ring
seat retainer. Impeller shaft to be 416SS fitted with a SS shaft sleeve
and be supported by two heavy duty ball bearings. The design shall allow
back pull out servicing, enabling the complete rotating assembly to
be removed without disturbing casing piping connections. The pump shall
be mounted on a rigid, single base plate and by flexible with guard
to the motor. Seal shall be rated for continuous duty at 270oF, motor
shall be open drip proof, NEMA MG-1 with 1.15 service factor
TRIPLE DUTY VALVE - System shall include, on the discharge
of each pump, a combination valve incorporating three functions in one
body: tight shut-off, spring closure type silent non-slam check, and
flow measured/throttling. Valve body shall be ductile icon with two
¼" NPT connections on each side of the valve seat. The valve
disc shall be bronze plug disc type with high impact engineered resin
seat to ensure tight shut-off and silent check valve operation. Valve
stem shall be SS with flat surfaces provided for adjustment with open
end wrench.
SUCTION DIFFUSER - System shall include, on the suction
of each pump a suction diffuser with cast iron body, outlet guide vanes
and removable SS strainer.
CONTROL PANEL - System shall include one (1) UL - Listed,
NEMA 12, Industrial Control Panel with single-point power connection,
pre-wired to all electrical components. Panel shall have thru-the-door
fused disconnect; magnetic circuit breaker supplementary motor protector
with fast-closing contacts, non-reversing 3-pole contactor, and variable
setting, bi-metallic overload relay for each motor; 30 mm Foundry-duty
switches; 30 mm Corrosion Resistant pilot lights; control transformer;
Automatic Alternator (if required). Operation of each pump shall be
Hand-Off-Auto with external connection to terminal blocks. When standby
pump(s) are used, the standby pump(s) shall manually/automatically(customer
specified) start on primary pump failure. All internal wiring shall
be placed in conduit.
MANUFACTURER - Shall assume system liability, and performance
guarantee and warranty all equipment on system for 12 months after initial
start-up.