Heat
Transfer System - Specifications
Furnish
and install one EnviroSep Model HTS- [A] - [B] - [C] - [D] Heat Transfer
System with the system capacity to heat ____ BTU/hr from 160 oF to 180
oF when ______ psig steam is available at the Heat Exchanger.
KEY:
[A]
= Model # (BTU/hr)
[B]
= # of pumps (1,2,3,etc.)
[C]
= Parallel (P) or Stand-by (S) pump designation
[D]
= Manual (M) or Automatic (A) alternation for multiple pumps
GENERAL
- This package shall be factory assembled with pump(s), heat exchanger,
hydronic accessories, shell and tube heat exchanger, fabricated steel
frame, interconnection piping( welded per ASME Section IX certified
welders), UL-listed Industrial Control Panel factory wired for single-point
field connection per NEC, and including Condensate Steam Trap.
PUMPS
- Pump(s) shall be single, end-suction type with radically split, top
center-line discharge, self-venting casing. Pump construction shall
be cast iron, bronze fitted and shall be fitted with a long-life, product
lubricated, drip tight mechanical seal, with O-ring seat retainer. Impeller
shaft to be 416SS fitted with a SS shaft sleeve and be supported by
two heavy duty ball bearings. The design shall allow back pull out servicing,
enabling the complete rotating assembly to be removed without disturbing
casing piping connections. The pump shall be mounted on a rigid, single
base plate and by flexible with guard to the motor. Seal shall be rated
for continuous duty at 270oF, motor shall be open drip proof, NEMA MG-1
with 1.15 service factor
HEAT
EXCHANGER- Heat exchanger shall be shell and tube type with removable
tube bundle. Shell is carbon steel with cast iron heads and tube sheets.
Tubes are ¾" OD copper. Unit is rated for 150 psig at 375
oF. Shell-side connections 4" and larger are 150 lb. ANSI flanges
and all 3" and smaller are NPT connection. Unit shall carry U-1
form and have ASME stamp for 150 psig operation.
AIR
REMOVAL EQUIPMENT- System shall include one tangential air separator
with internal stainless steel collector tube. Connections to be flanged
with a rating of 150 psig. System shall be equipped with ¾"
Pressure Relief Valve, ¾" Pressure Regulating Valve, ASME
Compression / Expansion Tank (sized by or provide system volume and
temperature difference), and tank fitting, sight glass, and tank drain
connections to tank.
TRIPLE
DUTY VALVE- System shall include, on the discharge of each pump, a combination
valve incorporating three functions in one body: tight shut-off, spring
closure type silent non-slam check, and flow measured/throttling. Valve
body shall be ductile icon with two ¼" NPT connections on
each side of the valve seat. The valve disc shall be bronze plug disc
type with high impact engineered resin seat to ensure tight shut-off
and silent check valve operation. Valve stem shall be SS with flat surfaces
provided for adjustment with open end wrench.
SUCTION
DIFFUSER- System shall include, on the suction of each pump a suction
diffuser with cast iron body, outlet guide vanes and removable SS strainer.
CONTROL
PANEL - System shall include one (1) UL - Listed, NEMA 12, Industrial
Control Panel with single-point power connection, pre-wired to all electrical
components. Panel shall have thru-the-door fused disconnect; magnetic
circuit breaker supplementary motor protector with fast-closing contacts,
non-reversing 3-pole contactor, and variable setting, bi-metallic overload
relay for each motor; 30 mm Foundry-duty switches; 30 mm Corrosion Resistant
pilot lights; control transformer; Automatic Alternator (if required).
Operation of each pump shall be Hand-Off-Auto with external connection
to terminal blocks. When standby pump(s) are used, the standby pump(s)
shall manually/automatically(customer specified) start on primary pump
failure. All internal wiring shall be placed in conduit.
STEAM
TRAP - Steam trap shall be of the mechanical ball float type with cast
iron body, NPT connections, and all stainless steel internals. A stainless
steel balanced pressure thermostatic air vent shall be incorporated
into the trap body withstanding 45° F of superheat and resisting
waterhammer without sustaining damage. Internals shall be serviceable
without disturbing piping.
MANUFACTURER
- Shall assume system liability, and performance guarantee and warranty
all equipment on system for 12 months after initial start-up.