Heat
Transfer System for use with Gas-fired Hot Water Boiler
- Specifications
Furnish and install one EnviroSep Model HTS-HWB- [A] - [B] - [C] -
[D] Heat Transfer System with the system capacity to heat ____ BTU/hr
from 160 oF to 180 oF when ______ psig steam is available at the Heat
Exchanger.
KEY:
[A] =
Model # (BTU/hr)
[B] =
# of pumps (1,2,3,etc.)
[C] =
Parallel (P) or Stand-by (S) pump designation
[D] =
Manual (M) or Automatic (A) alternation for multiple pumps
GENERAL
- This package shall be factory assembled with pump(s), heat exchanger,
hydronic accessories, shell and tube heat exchanger, fabricated steel
frame, interconnection piping( welded per ASME Section IX certified
welders), UL-listed Industrial Control Panel factory wired for single-point
field connection per NEC, and including Condensate Steam Trap.
PUMPS
- Pump(s) shall be single, end-suction type with radically split,
top center-line discharge, self-venting casing. Pump construction
shall be cast iron, bronze fitted and shall be fitted with a long-life,
product lubricated, drip tight mechanical seal, with O-ring seat retainer.
Impeller shaft to be 416SS fitted with a SS shaft sleeve and be supported
by two heavy duty ball bearings. The design shall allow back pull
out servicing, enabling the complete rotating assembly to be removed
without disturbing casing piping connections. The pump shall be mounted
on a rigid, single base plate and by flexible with guard to the motor.
Seal shall be rated for continuous duty at 270oF, motor shall be open
drip proof, NEMA MG-1 with 1.15 service factor
HOT WATER
BOILER - The Boiler shall operate on negative stack pressure and Category
I according to ANSI Standards and shall include a built-in draft hood
with single exhaust (standard) or dual exhaust. The boiler shall be
equipped with a slide-out Burner tray for service and maintenance.
The combustion chamber shall be enclosed by high temperature refractory,
not less than 2 ½" thickness. The heat exchanger shall
be an integral copper finned tube, straight, 7/8" ID, 7 fins
per inch. Standard controls include thermometers, High Limit controls,
ON/OFF switch, 24VAC control transformer, and factory-mounted flow
switch interlocked to pump operation. Standard firing-mode shall be
ON/OFF. The gas train shall include manual gas valve, redundant main
gas valves, pilot gas pressure regulator, and automatic pilot gas
valve.
AIR REMOVAL
EQUIPMENT- System shall include one tangential air separator with
internal stainless steel collector tube. Connections to be flanged
with a rating of 150 psig. System shall be equipped with ¾"
Pressure Relief Valve, ¾" Pressure Regulating Valve, ASME
Compression / Expansion Tank (sized by or provide system volume and
temperature difference), and tank fitting, sight glass, and tank drain
connections to tank.
TRIPLE
DUTY VALVE- System shall include, on the discharge of each pump, a
combination valve incorporating three functions in one body: tight
shut-off, spring closure type silent non-slam check, and flow measured/throttling.
Valve body shall be ductile icon with two ¼" NPT connections
on each side of the valve seat. The valve disc shall be bronze plug
disc type with high impact engineered resin seat to ensure tight shut-off
and silent check valve operation. Valve stem shall be SS with flat
surfaces provided for adjustment with open end wrench.
SUCTION
DIFFUSER- System shall include, on the suction of each pump a suction
diffuser with cast iron body, outlet guide vanes and removable SS
strainer.
CONTROL
PANEL - System shall include one (1) UL - Listed, NEMA 12, Industrial
Control Panel with single-point power connection, pre-wired to all
electrical components. Panel shall have thru-the-door fused disconnect;
magnetic circuit breaker supplementary motor protector with fast-closing
contacts, non-reversing 3-pole contactor, and variable setting, bi-metallic
overload relay for each motor; 30 mm Foundry-duty switches; 30 mm
Corrosion Resistant pilot lights; control transformer; Automatic Alternator
(if required). Operation of each pump shall be Hand-Off-Auto with
external connection to terminal blocks. When standby pump(s) are used,
the standby pump(s) shall manually/automatically(customer specified)
start on primary pump failure. All internal wiring shall be placed
in conduit.
MANUFACTURER
- Shall assume system liability, and performance guarantee and warranty
all equipment on system for 12 months after initial start-up.
\