Heat Transfer Systems (HTS)

Heat Transfer System

The Model HTS, Heat Transfer System is a UL-listed factory assembled and tested system used in conventional building hydronic heating system which utilizes steam as the heating source. Hot water is supplied at a standard 180oF and is recirculated through the building system by use of centrifugal pump which are sized to meet specific building requirements. The Model HTS provides air-free hot water at a controlled flow rate, while automatically refilling under normal system losses. The HTS also allows for system thermal expansion/compression based on the building system volume. A UL-listed control panel with single-point power connection is prewired to all electrical sources. Each Unit is custom engineered and designed to meet specific system requirements. All systems are fabricated and welded per ASME Section IX Code and Standards, and are Hydrostatically tested prior to shipment. The Model HTS speeds installation and start-up of building hydronic heating systems which provide significant savings to contractors, engineers, and building owners.


View Heat Transfer System specifications

View detailed information on Model HTS, Heat Transfer System (PDF)


Standard Construction

  • Structural Channel Base
  • Carbon Steel Piping
  • Operational Testing
  • Pump Isolation Valves
  • Hydrostatically Tested
  • High Temperature Industrial Enamel Paint

Legend

A. Base-mounted, End-Suction Centrifugal Pumps
B. Shell and Tube , U-tube Heat Exchanger with Steam Trap
C. Triple Duty Valve
D. Air Separator with auto air vent
E. Expansion / Compression Tank
F. System Inlet / Outlet Thermometers
G. Pump Differential Pressure Gauge
H. UL-listed Electrical Control Panel
I. Make-up Water Assembly


  • System Options
  • Stand-by pumps
  • Suction Diffuser
  • Panel mounted Gauges
  • Flexible connectors
  • Vibration Isolation

Conditions of Operation
Max. Allowable Pressure: 125 psig / 8.6 bar
Max. Allowable Temperature: 375 oF / 190.5 oC

 


For more information on how EnviroSep can provide your company with
an Integrated Solution for your Fluids Handling, Heat Transfer, and/or Energy Recovery needs, use our quick & easy Online Quote Request Form, call our main office at 843-546-7400 (you can fax us at 843.546.7407) or


domestic water pumps | hot water pumps | steam & condensate pumps | boiler room pumps | wastewater heat recovery pumps | packaged pumps | misc. industrial pumps | electrical & pump controls | custom pumps | private label pumps || site map


© 1999-2008 Copyright — EnviroSep — a division of TMT, Inc., Georgetown, South Carolina   USA
EnviroSep is an American Manufacturer of Pre-Engineered or Packaged Fluid Handling, Heat Transfer, and Energy Recovery
Systems