Industrial Process & Specialty Systems Process Cooling Water Systems Commercial HVAC Pumping & Heat Transfer Systems Modular Chiller & HW Boiler Plants Hot Water Heating Systems Boiler Room, Steam & Condensate Systems Domestic Water Booster Pump Systems Wastewater Heat Recovery ASME Pressure Vessels & Custom Systems Electrical PLC & Controls Process Engineering & Custom Solutions Private Label Systems
PICS: Industrial Process & Specialty Systems PICS: Process Cooling Water Systems PICS: Commercial HVAC Pumping & Heat Transfer Systems PICS: Modular Chiller & HW Boiler Plants PICS: Hot Water Heating Systems PICS: Boiler Room, Steam & Condensate Systems PICS: Domestic Water Booster Pump Systems PICS: Wastewater Heat Recovery PICS: ASME Pressure Vessels & Custom Systems PICS: Electrical PLC & Controls
Company Overview (PDF) Line Card (PDF) Technical Library
Welcome to EnviroSep!
Phone: 843-546-7400
Providing Integrated Solutions, Worldwide, for Fluids Handling, Heat Transfer & Energy Recovery
| site map

Specifications:
Closed Loop Heat Transfer Unit with Steam Powered Condensate Pump (HTUC)

Furnish and install one EnviroSep Model HTUC - [A] - [B] - [C] - [D] - [E] - [F] - [G] - [H] Heat Transfer Unit with unit capacity to heat ____ gpm from _____ oF to _____ oF when ______ psig steam is available at the factory installed, Steam Control Valve.

KEY:
[A] = System Flow Rate (gpm)
[B] = Inlet Temperature (oF )
[C] = Outlet Temperature (oF )
[D] = Steam Pressure at Control Valve
[E] = Pressure Drop (psid)
[F] = Motive Steam Pressure (psig)
[G] = Condensate Back Pressure (psig)
[H] = Fouling Factor



GENERAL - This unit shall be factory assembled with steam control valve, steam trap, shell and tube heat exchanger, fabricated steel frame, interconnection piping (welded per ASME Section IX certified welders), UL-listed Industrial Control Panel factory wired for single-point field connection per NEC, ( if required).

HEAT EXCHANGER - Heat exchanger shall be shell and tube type with removable tube bundle. Shell is carbon steel with cast iron heads and tube sheets. Tubes are 3/4" OD copper. Unit is rated for 150 psig at 375 oF. Shell-side connections 4" and larger are 150 lb. ANSI flanges and all 3" and smaller are NPT connection. Unit shall carry U-1 form and have ASME stamp for 150 psig operation.

FLOAT & THERMOSTATIC STEAM TRAP - Steam trap shall be of the mechanical ball float type with cast iron body, NPT connections, and all stainless steel internals. A stainless steel balanced pressure thermostatic air vent shall be incorporated into the trap body withstanding 45 oF of superheat and resisting waterhammer without sustaining damage. Internals shall be serviceable without disturbing piping.

PILOT-OPERATED STEAM CONTROL VALVE - The control valve shall be pilot-actuated, diaphragm-operated, and shall be single-seated, with hardened stainless steel trim and cast iron body. The pilot shall be bolted directly to the valve body and shall be removable without disturbing control connections. The temperature setting shall be adjustable and indicated on a calibrated dial. Temperature sensor shall be solid fill.

PNEUMATIC- OPERATED STEAM CONTROL VALVE - The control valve shall be pneumatically actuated with valve body constructed of cast iron and having stainless steel plug, seat, and stem. The pneumatic actuator shall be of the spring-closed design and shall have a fabric reinforced nitrile rubber diaphragm. Actuator yoke shall incorporate electro-pneumatic, intrinsically safe positioner requiring a 4-20 ma input signal, and compressed air connection for valve operation. The positioner shall compare the electrical signal from a controller with the valve position feedback to overcome varying differential pressure, stem friction, and diaphragm hysterisis.

STEAM-POWERED CONDENSATE PUMP - Pump shall be low profile, steam-powered, operated by steam up to 125 psig, not requiring any electrical energy, and safe for use in flammable atmospheres. Body construction shall be cast iron. The pump shall contain a float operated snap-action mechanism with no external seals or packing, stainless steel trim, and hardened bearing components. Pump shall include stainless steel Inlet and Outlet check valves, and gauge glass.

MANUFACTURER - Shall assume system liability, and performance guarantee and warranty all equipment on system for 12 months after initial start-up.

For more information on how EnviroSep can provide your company with an Integrated Solution for your Fluids Handling, Heat Transfer, and/or Energy Recovery needs, use our quick & easy Online Quote Request Form, call our main office at 843-546-7400 (you can fax us at 843.546.7407) or