FAQ's What's New? Careers & Employment Newsletters Newsletter Sign Up
Industrial Process & Specialty Systems Process Cooling Water Systems Commercial HVAC Pumping & Heat Transfer Systems Modular Chiller & HW Boiler Plants Hot Water Heating Systems Boiler Room, Steam & Condensate Systems Domestic Water Booster Pump Systems Wastewater Heat Recovery ASME Pressure Vessels & Custom Systems Electrical PLC & Controls Process Engineering & Custom Solutions Private Label Systems
PICS: Industrial Process & Specialty Systems PICS: Process Cooling Water Systems PICS: Commercial HVAC Pumping & Heat Transfer Systems PICS: Modular Chiller & HW Boiler Plants PICS: Hot Water Heating Systems PICS: Boiler Room, Steam & Condensate Systems PICS: Domestic Water Booster Pump Systems PICS: Wastewater Heat Recovery PICS: ASME Pressure Vessels & Custom Systems PICS: Electrical PLC & Controls
Company Overview (PDF) Line Card (PDF) Technical Library
Welcome to EnviroSep!
Phone: 843-546-7400
Providing Integrated Solutions, Worldwide, for Fluids Handling, Heat Transfer & Energy Recovery
| site map

your location: » home » products » Hot Water Heating Systems » Hot Water Converters » Heat Transfer Unit with Steam-Powered Condensate Pump (HTUP)

 
5 Hot Water Heating Systems

Heat Transfer Unit with Steam-Powered Condensate Pump (HTUP)

The Model HTUP, Heat Transfer Unit with integrally assembled steam-powered condensate pump is a complete manufactured system providing efficient heat transfer, steam utilization, and condensate removal. The Model HTUP unit features an ASME Shell and Tube, U-tube, Heat Exchanger; Pilot-operated Steam Control Valve; and Steam-Powered Condensate Pump with motive steam and exhaust connections. Each Unit is custom engineered and designed to meet specific system requirements. All systems are fabricated and welded per ASME Section IX Code and Standards, and are Hydrostatically tested prior to shipment.


View HTUP Specifications

View detailed information on Heat Transfer Unit with Steam-Powered Condensate Pump (PDF)

Legend:
A. Inlet Steam Y- Strainer

B. Steam Control Valve (Pilot-Operated or Pneumatic-Operated)

C. Shell and Tube Heat Exchanger

D. Inverted Bucket Steam Trap

E. Steam-powered Condensate Pump


Standard Construction
  • Fabricated Floor-mount Steel Base and frame
  • ASME Shell and Tube, U-Tube Heat Exchanger
  • Inlet Steam Y-Strainer
  • Cast Iron Inverted Bucket Steam Trap with Air Vent
  • Cast Iron Pilot-operated Temperature Control Valve with 8ft. capillary tube connected to Temperature Sensor
  • Steam-powered Condensate Pump
  • Motive Steam Connection with Drip Leg Station
  • Pump Exhaust pre-installed
  • Hydrostatically Tested
  • High Temperature Industrial Enamel Paint

    Sizing and Selection
    Units are custom engineered for individual systems, based upon the selection of the system parameters:

    I. System Flow Rate: Range of 5 gpm to 2,000 gpm

    II. Inlet Temperature: Range of 40oF to 160oF

    III. Outlet Temperature: Range of 120oF to 320oF

    IV. Steam Pressure: Range of 2 psig to 125 psig

    V. Dimensions: Based on specific requirements



    Conditions of Operation
    Max. Allowable Pressure: 125 psig / 8.6 bar
    Max. Allowable Temperature: 375 oF / 190.5 oC
    Note: Condensate back pressure is assumed at 0 psig unless otherwise specified.

For more information on how EnviroSep can provide your company with an Integrated Solution for your Fluids Handling, Heat Transfer, and/or Energy Recovery needs, use our quick & easy Online Quote Request Form, call our main office at 843-546-7400 (you can fax us at 843.546.7407) or