EnviroSep Model HTS-VF, Variable Flow Heat Transfer System provides significant power savings by automatically controlling pump(s) speed based on the actual building system demand. Typically, Differential Pressure Transmitters are placed across the building heating system zone loops, signaling the Variable Speed Controller to operate the pumps at the appropriate conditions to meet demand. The Model HTS-VF may be controlled by other system variables, such as Total System Load (BTU/hr), System Pressure, or System Temperature via a customized Controller. Variable Frequency Drives may be incorporated with Manual or Automatic Bypasses. A User-friendly, Color Touch Screen Operator Interface and Non-proprietary, PLC-based Controller is utilized for simple operation. The Model HTS-VF Controller may be furnished with Interface to any Building Management System. This fully integrated turn-key system speeds installation and start-up which provides significant, initial-investment savings to contractors, engineers, and building owners.
Standard Features:
- ASME, Shell & Tube Heat Exchanger - U-tube, with U-stamp
- Base-mounted, End-suction Pumps
- Variable Frequency Drives & Controller
- Differential Pressure Transmitters
- Vortex Air Separator, with Auto Air Vent
- Bladder Expansion/Compression Tank
- Triple Duty Valves & Suction Diffusers
- UL Listed NEMA 12 Industrial Control Panel
- Float & Thermostatic Steam Trap
- Pilot-operated, Motor-operated, or Pneumatic-operated Control Valves
- Make-up Water Assembly, with Safety Relief Valve
- Microprocessor based Temperature Controller, if required
Options:
- Internet Connectivity for Remote System Monitoring
- Interface w/ Building Management System
- NEMA 3R/4/4X Rating
- Seismic or Vibration Isolators
- Combination Air & Dirt Separator
- Specific Performance Criteria (Upon Request)

|
|