FAQ's What's New? Careers & Employment Newsletters Newsletter Sign Up
Industrial Process & Specialty Systems Process Cooling Water Systems Commercial HVAC Pumping & Heat Transfer Systems Modular Chiller & HW Boiler Plants Hot Water Heating Systems Boiler Room, Steam & Condensate Systems Domestic Water Booster Pump Systems Wastewater Heat Recovery ASME Pressure Vessels & Custom Systems Electrical PLC & Controls Process Engineering & Custom Solutions Private Label Systems
PICS: Industrial Process & Specialty Systems PICS: Process Cooling Water Systems PICS: Commercial HVAC Pumping & Heat Transfer Systems PICS: Modular Chiller & HW Boiler Plants PICS: Hot Water Heating Systems PICS: Boiler Room, Steam & Condensate Systems PICS: Domestic Water Booster Pump Systems PICS: Wastewater Heat Recovery PICS: ASME Pressure Vessels & Custom Systems PICS: Electrical PLC & Controls
Company Overview (PDF) Line Card (PDF) Technical Library
Welcome to EnviroSep!
Call Us @ 843-546-7400
Providing Integrated Solutions, Worldwide, for Fluids Handling, Heat Transfer & Energy Recovery
| site map

Specifications - Packaged Pumping System for Open Systems: PPS-O

Furnish and install one EnviroSep Model PPS-O- [A] - [B] - [C] - [D] Packaged Pumping System with the system capacity to pump _________ GPM of _____________ (fluid) from __________psig to __________psig. .

KEY:
[A] = Model # (GPM)
[B] = # of pumps (1,2,3,etc.)
[C] = Parallel (P) or Stand-by (S) pump designation
[D] = Manual (M) or Automatic (A) alternation for multiple pumps
GENERAL - This package shall be factory assembled with pump(s), fabricated steel frame, interconnection piping( welded per ASME Section IX certified welders), UL-listed Industrial Control Panel factory wired for single-point field connection per NEC.

PUMPS-Pump(s) shall be single, end-suction type with radically split, top center-line discharge, self-venting casing. Pump construction shall be cast iron, bronze fitted and shall be fitted with a long-life, product lubricated, drip tight mechanical seal, with O-ring seat retainer. Impeller shaft to be 416SS fitted with a SS shaft sleeve and be supported by two heavy duty ball bearings. The design shall allow back pull out servicing, enabling the complete rotating assembly to be removed without disturbing casing piping connections. The pump shall be mounted on a rigid, single base plate and by flexible with guard to the motor. Seal shall be rated for continuous duty at 270oF, motor shall be open drip proof, NEMA MG-1 with 1.15 service factor

TRIPLE DUTY VALVE- System shall include, on the discharge of each pump, a combination valve incorporating three functions in one body: tight shut-off, spring closure type silent non-slam check, and flow measured/throttling. Valve body shall be ductile icon with two ¼” NPT connections on each side of the valve seat. The valve disc shall be bronze plug disc type with high impact engineered resin seat to ensure tight shut-off and silent check valve operation. Valve stem shall be SS with flat surfaces provided for adjustment with open end wrench.

BUTTERFLY VALVES - System Butterfly Isolation Valves shall be Lug-mounted, Cast Iron with 10-position Lever Operator for 6” and below; and Gear Operated above 6” in size. Disc shall be Al-Br or Stainless Steel. Seat material shall be Buna-N or EPDM.

BALL VALVE - Isolation Ball Valves shall be Bronze 2-pc with 316L Stainless Steel Ball and RTFE seats. All Valves shall have Latch-lock lever for Lock-Out procedures.

SUCTION DIFFUSER- System shall include, on the suction of each pump a suction diffuser with cast iron body, outlet guide vanes and removable SS strainer.

CONTROL PANEL - System shall include one (1) UL - Listed, NEMA 12, Industrial Control Panel with single-point power connection, pre-wired to all electrical components. Panel shall have thru-the-door fused disconnect; magnetic circuit breaker supplementary motor protector with fast-closing contacts, non-reversing 3-pole contactor, and variable setting, bi-metallic overload relay for each motor; 30 mm Foundry-duty switches; 30 mm Corrosion Resistant pilot lights; control transformer; Automatic Alternator (if required). Operation of each pump shall be Hand-Off-Auto with external connection to terminal blocks. When standby pump(s) are used, the standby pump(s) shall manually/automatically (customer specified) start on primary pump failure. All internal wiring shall be placed in conduit.

MANUFACTURER - Shall assume system liability, and performance guarantee and warranty all equipment on system for 12 months after initial start-up.


V090308
 
For more information on how EnviroSep can provide your company with an Integrated Solution for your Fluids Handling, Heat Transfer, and/or Energy Recovery needs, use our quick & easy Online Quote Request Form, call our main office at 843-546-7400 (you can fax us at 843.546.7407) or