FAQ's What's New? Careers & Employment Newsletters Newsletter Sign Up
Industrial Process & Specialty Systems Process Cooling Water Systems Commercial HVAC Pumping & Heat Transfer Systems Modular Chiller & HW Boiler Plants Hot Water Heating Systems Boiler Room, Steam & Condensate Systems Domestic Water Booster Pump Systems Wastewater Heat Recovery ASME Pressure Vessels & Custom Systems Electrical PLC & Controls Process Engineering & Custom Solutions Private Label Systems
PICS: Industrial Process & Specialty Systems PICS: Process Cooling Water Systems PICS: Commercial HVAC Pumping & Heat Transfer Systems PICS: Modular Chiller & HW Boiler Plants PICS: Hot Water Heating Systems PICS: Boiler Room, Steam & Condensate Systems PICS: Domestic Water Booster Pump Systems PICS: Wastewater Heat Recovery PICS: ASME Pressure Vessels & Custom Systems PICS: Electrical PLC & Controls
Company Overview (PDF) Line Card (PDF) Technical Library
Welcome to EnviroSep!
Phone: 843-546-7400
Providing Integrated Solutions, Worldwide, for Fluids Handling, Heat Transfer & Energy Recovery
| site map

your location: » home » products » Boiler Room, Steam & Condensate Systems » Blowdown Flash Vessel with Heat Recovery > Heat Recovery on Condensate (FSHR-C)

Heat Recovery on Condensate (FSHR-C) - Flash Steam Heat Recovery Unit (Condensate)

Legend
A. Flash Vessel
B. Plate and Frame Recovery Module
C. Vent
D. Blowdown Inlet
E. Make-up Water Inlet
F. Heated Make-up Water Supply
G. Condensate Discharge
H. Steam Trap

The Model FSHR-C, Flash Steam Heat Recovery Unit is a manufactured unit featuring a Recovery Module facilitating condensate heat extraction from boiler blowdown. The FSHR-C is ideally suited for heating continuous flow of fluid, such as make-up water to boiler feedwater system.

The atmospherically vented unit helps recovery and utilize valuable heat generally lost during boiler blowdown. A Shell and Tube Recovery Module with U-tube configuration is used for the condensate; Plate and Frame Module is optional. The Model FSHR-C is a complete unit including a Carbon Steel Flash Vessel. Non-continuous flow applications may require additional recirculation and/or relief valving. An optional make-up water control valve may be installed upstream of the unit in order for the make-up to be allowed to thermally expand to atmosphere to prevent system damage.

Each Unit is custom engineered and designed to meet specific system requirements. All systems are fabricated and welded per ASME Section IX Code and Standards, and are Hydrostatically tested prior to shipment.


View detailed information on Model FSHR-C, Flash Steam Heat Recovery Unit (PDF)


Standard Construction
  • Fabricated Structural Steel frame
  • Plate and Frame Recovery Module
  • Carbon Steel Flash Vessel
  • Hydrostatically Tested
  • High Temperature Industrial Enamel Paint

Sizing and Selection
Units are custom engineered for individual systems, based upon the selection of the system parameters:

I. System Flow Rate: Range of 5 lb/hr to 30,000 lb/hr

II. Blow-down Upstream Pressure: Range of 5 psig to 250 psig

III. Flash Vessel Pressure: Range of 0 psig to 15psig

IV. Dimensions: Based on specific requirements


Conditions of Operation
Max. Allowable Pressure: 125 psig
Max. Allowable Temperature: 375 oF

For more information on how EnviroSep can provide your company with an Integrated Solution for your Fluids Handling, Heat Transfer, and/or Energy Recovery needs, use our quick & easy Online Quote Request Form, call our main office at 843-546-7400 (you can fax us at 843.546.7407) or