EECP-D
Specifications — Economy Electric Condensate Pump Package - Specifications
Furnish and install one EnviroSep Model EECP- [A] - [B] - [C] - [D]
Electric Condensate Pump Package with the system capacity to pump ____________
lb/hr at a discharge pressure of ______ psig from the pump(s).
KEY:
[A]
= Model # (Nominal Flow from each pump- GPM)
[B] = # of pumps (1 = S, 2 = D, 3 = T, 4 = Q)
[C] = Parallel (P) or Stand-by (S) pump designation
[D] = Mechanical (M) or Electric (E) alternation for multiple pumps
GENERAL
- This package shall be factory assembled with pump(s), condensate receiver,
pump suction isolation valves, fabricated steel frame, mechanical alternator
(where applicable) interconnection piping (welded per ASME Section IX
certified welders), (optional) UL-listed Industrial Control Panel factory
wired for single-point field connection per NEC, and the complete package
shall be UL-Listed as a Packaged Pumping System.
PUMPS
- Pump(s) shall be a Stainless Steel, End Suction Centrifugal Pump(s)
with a capacity of _____ GPM @ _____ psig discharge head. The maximum
speed of the pump shall not exceed 1750 RPM. Pump shall be of the vertically
split case design with removable bearing housings and shall be furnished
with mechanical seals. The suction connection shall be in the top vertical
position and the discharge connection shall be in the top horizontal
position. The impeller(s) shall be located on a stainless steel shaft
between sealed grease lubricated ball bearings. The pump shall be mounted
on a rigid, single base plate and by flexible with guard to the motor.
Seal shall be rated for continuous duty at 240oF, motor shall be open
drip proof, NEMA MG-1 with 1.15 service factor
CONDENSATE
RECEIVER - Condensate Receiver shall be constructed of polished, 304L
Stainless Steel and shall be GTAW welded per ASME Section IX certified
welders. The receiver shall have the capacity of __ gallons and shall
be of the vertical-mounted design. The mounting height of the receiver
shall be of adequate height to permit a minimum of 2 ft. NPSH available
to the system pumps when the condensate temperature is 200oF. The receiver
shall be supported by rigid structural steel supports to adequately
support the receiver when completely full of water. Connections shall
be provided for Atmospheric Vent, Condensate Inlet, Pump Suction Connections,
Receiver Drain connection, two (2) auxiliary connections, and connection
for internally-mounted mechanical alternator.
MECHANICAL
FLOAT SWITCH - System shall include, on the receiver, a combination
float switch, mechanical alternator which shall be horizontally mounted
in the receiver. The alternator shall be NEMA I, Square D Series 9038,
(with) (without) auxiliary standby float switch. The alternator shall
automatically alternate the lead pump of the system and shall automatically
start all system pumps as the system demand requires.
CONTROL
PANEL - System shall include one (1) UL - Listed, NEMA 12, Industrial
Control Panel with single-point power connection, pre-wired to all electrical
components. Panel shall have thru-the-door fused disconnect; magnetic
circuit breaker supplementary motor protector with fast-closing contacts,
non-reversing 3-pole contactor, and variable setting, bi-metallic overload
relay for each motor; 30 mm Foundry-duty switches; 30 mm Corrosion Resistant
pilot lights; control transformer; Automatic Alternator (if required).
Operation of each pump shall be Hand-Off-Auto with external connection
to terminal blocks. When standby pump(s) are used, the standby pump(s)
shall manually/automatically(customer specified) start on primary pump
failure. All internal wiring shall be placed in conduit.
MANUFACTURER
- Shall assume system liability, and performance guarantee and warranty
all equipment on system for 12 months after initial start-up.
Return
to Economy Electric Condensate
Pump Package: Model EECP-S
Return
to Economy Electric Condensate
Duplex Pump Package : Model EECP-D |