Stainless
Steel Receiver Electric Condensate Pumps (UL Listed) Model
ECP-S
Electric
Condensate Pump Package - Specifications
Furnish and install one EnviroSep Model ECP- [A] - [B] - [C] - [D]
Electric Condensate Pump Package with the system capacity to pump
____________ lb/hr at a discharge pressure of ______ psig from the
pump(s).
KEY:
[A] =
Model # (Nominal Flow from each pump- GPM)
[B] =
# of pumps (1 = S, 2 = D, 3 = T, 4 = Q)
[C] =
Parallel (P) or Stand-by (S) pump designation
[D] =
Mechanical (M) or Electric (E) alternation for multiple pumps
GENERAL - This package shall be factory assembled with pump(s), condensate
receiver, pump suction isolation valves, fabricated steel frame, mechanical
alternator (where applicable) interconnection piping (welded per ASME
Section IX certified welders), (optional) UL-listed Industrial Control
Panel factory wired for single-point field connection per NEC, and
the complete package shall be UL-Listed as a Packaged Pumping System.
PUMPS - Pump(s) shall be a Stainless Steel, Vertical Multi-staged,
Centrifugal Pump(s) with a capacity of _____ GPM @ _____ psig discharge
head. The maximum speed of the pump shall not exceed 1750 RPM. Pump
shall be of the vertically split case design with removable bearing
housings and shall be furnished with mechanical seals. The suction
connection shall be in the top vertical position and the discharge
connection shall be in the top horizontal position. The impeller(s)
shall be located on a stainless steel shaft between sealed grease
lubricated ball bearings. The pump shall be mounted on a rigid, single
base plate and by flexible with guard to the motor. Seal shall be
rated for continuous duty at 240oF, motor shall be open drip proof,
NEMA MG-1 with 1.15 service factor
CONDENSATE
RECEIVER - Condensate Receiver shall be constructed of polished, 304L
Stainless Steel and shall be GTAW welded per ASME Section IX certified
welders. The receiver shall have the capacity of __ gallons and shall
be of the vertical-mounted design. The mounting height of the receiver
shall be of adequate height to permit a minimum of 2 ft. NPSH available
to the system pumps when the condensate temperature is 200oF. The
receiver shall be supported by rigid structural steel supports to
adequately support the receiver when completely full of water. Connections
shall be provided for Atmospheric Vent, Condensate Inlet, Pump Suction
Connections, Receiver Drain connection, two (2) auxiliary connections,
and connection for internally-mounted mechanical alternator.
MECHANICAL
FLOAT SWITCH - System shall include, on the receiver, a combination
float switch, mechanical alternator which shall be horizontally mounted
in the receiver. The alternator shall be NEMA I, Square D Series 9038,
(with) (without) auxiliary standby float switch. The alternator shall
automatically alternate the lead pump of the system and shall automatically
start all system pumps as the system demand requires.
CONTROL
PANEL - System shall include one (1) UL - Listed, NEMA 12, Industrial
Control Panel with single-point power connection, pre-wired to all
electrical components. Panel shall have thru-the-door fused disconnect;
magnetic circuit breaker supplementary motor protector with fast-closing
contacts, non-reversing 3-pole contactor, and variable setting, bi-metallic
overload relay for each motor; 30 mm Foundry-duty switches; 30 mm
Corrosion Resistant pilot lights; control transformer; Automatic Alternator
(if required). Operation of each pump shall be Hand-Off-Auto with
external connection to terminal blocks. When standby pump(s) are used,
the standby pump(s) shall manually/automatically(customer specified)
start on primary pump failure. All internal wiring shall be placed
in conduit.
MANUFACTURER
- Shall assume system liability, and performance guarantee and warranty
all equipment on system for 12 months after initial start-up.