Industrial Process & Specialty Systems Process Cooling Water Systems Commercial HVAC Pumping & Heat Transfer Systems Modular Chiller & HW Boiler Plants Hot Water Heating Systems Boiler Room, Steam & Condensate Systems Domestic Water Booster Pump Systems Wastewater Heat Recovery ASME Pressure Vessels & Custom Systems Electrical PLC & Controls Process Engineering & Custom Solutions Private Label Systems
PICS: Industrial Process & Specialty Systems PICS: Process Cooling Water Systems PICS: Commercial HVAC Pumping & Heat Transfer Systems PICS: Modular Chiller & HW Boiler Plants PICS: Hot Water Heating Systems PICS: Boiler Room, Steam & Condensate Systems PICS: Domestic Water Booster Pump Systems PICS: Wastewater Heat Recovery PICS: ASME Pressure Vessels & Custom Systems PICS: Electrical PLC & Controls
Company Overview (PDF) Line Card (PDF) Technical Library
Welcome to EnviroSep!
Phone: 843-546-7400
Providing Integrated Solutions, Worldwide, for Fluids Handling, Heat Transfer & Energy Recovery
| site map

your location: » home » products » Boiler Room, Steam & Condensate Systems » Blowdown Separator with Vent Head and Cooling Valve

Blowdown Separator with Vent Head and Cooling Valve

The Model BDS, Boiler Blowdown Separator is a manufactured unit used for after-cooling of boiler blowdown or condensate before discharge to Sanitary Sewer. The BDS is ideally suited for reducing wastewater temperature of continuous blowdown discharge to municipal sewers. Atmospherically vented, the Model BDS is a complete unit including a Carbon Steel Separator, a Make-up Water Capillary-style Temperature Control Valve, and Vent Head. Each Unit is custom engineered and designed to meet specific system requirements. All systems are fabricated and welded per ASME Section IX Code and Standards, and are Hydrostatically tested prior to shipment.

View detailed information on Model BDS, Boiler Blowdown Separator (PDF)

 

 

Legend

A. Carbon Steel Receiver

B. Vent Head

C. Make-up Water Inlet

D. Capillary-style Temperature Control Valve

E. Blowdown Inlet

F. Blended Discharge

Sizing and Selection
Units are custom engineered for individual systems, based upon the selection of the system parameters:

I. System Flow Rate: Range of 5 lb/hr to 30,000 lb/hr

II. Blow-down Upstream Pressure: Range of 5 psig to 250 psig

III. Flash Vessel Pressure: Range of 0 psig to 15psig

IV. Dimensions: Based on specific requirements

Standard Construction
  • Fabricated Structural Steel Frame
  • Capillary-style Temperature Control Valve
  • Carbon Steel Flash Vessel
  • Hydrostatically Tested
  • High Temperature Industrial Enamel Paint

System Options
  • System Inlet / Outlet Thermometers
  • Stainless Steel Construction
  • Oversized Connections

Conditions of Operation

  • Max. Allowable Pressure: 125 psig
  • Max. Allowable Temperature: 375° F.



For more information on how EnviroSep can provide your company with an Integrated Solution for your Fluids Handling, Heat Transfer, and/or Energy Recovery needs, use our quick & easy Online Quote Request Form, call our main office at 843-546-7400 (you can fax us at 843.546.7407) or